Electric Power 10KV Medium Voltage Cable XLPE Insulated Underground Power Cable
Electric Power 10KV Medium Voltage Cable XLPE Insulated Underground Power Cable
Standard:
IEC60502, BS6346, VDE, AS/NZS, UL,etc
The Rated Voltage(kv):
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
Number of cores:
1, 3,
Construction:
Conductor: Solid or stranded copper/aluminum
Insulation: Cross-linked polyethylene (XLPE) or Polyvinyl chloride (PVC)
Filler: Polypropylene filament with lapped binding tape
Binder: Binding tape
Inner sheath: Polyvinyl chloride (PVC)
Amour: Galvanized steel wire armored(SWA) or steel tape armored(STA)
Sheath: Polyvinyl chloride (PVC)
Sectional Area:
25 mm2 , 35 mm2 , 50 mm2 ,70 mm2 , 95 mm2 ,120 mm2 ,150 mm2 ,185 mm2 ,240 mm2 ,300 mm2 400 mm2 500 mm2 630 mm2 800 mm2
Type Name Main Application
Cu core Al core
YJV
YJY YJLV
YJLV XLPE insulated, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and underground. Unable to bear external mechanical force, but bear the traction force during laid
YJV22
YJV22 YJLV22
YJV22 XLPE Insulated, Steel Tape Armored, PVC or PE Sheathed Power Cable For laying indoor, tunnel, channel and underground. Able to bear external mechanical force, but unable to bear large pulling force
YJV32
YJV32 YJLV32
YJLV32 XLPE Insulated, Fine Steel Wire Armored, PVC or PE Sheathed Power Cable For laying in shaft with large difference of level. Able to bear external mechanical force and moderate pulling force
YJV42YJV42 YJLV42YJLV42 XLPE Insulated, Thick Steel Wire Armored, PVC or PE Sheathed Power Cable Able to bear positive pressure and pulling force
Note: "ZR-" includes ABC three kinds of flame retardent cables, which are respectively indicated in "ZRA-" or "ZRB-" "ZRC-". For example: "ZRB-YJV", "ZRA-YJV22".
Rated Voltage, No. of Core and Range of Sectional Area
Rated voltage (kv)
Sectional area (mm2)
No. of core 1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
1 Core 1.5-800 25-800 25-1200 25-1200 35-1200 50-1200 50-1200 50-1200
3 Core 1.5-400 25-400 25-400 25-400 35-400 50-400 50-400 50-400
Main Technical Quota
DC resistance: conductor resistance of finished cable at 20℃ per kilometer is not more than the following values.
Nominal section area (mm2) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
Copper core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221
Aluminum core 18.1 12.1 7.41 4.61 3.08 1.91 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.778 0.0605 0.0469 0.0367
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
Number of cores:
Insulation: Cross-linked polyethylene (XLPE) or Polyvinyl chloride (PVC)
Filler: Polypropylene filament with lapped binding tape
Binder: Binding tape
Inner sheath: Polyvinyl chloride (PVC)
Amour: Galvanized steel wire armored(SWA) or steel tape armored(STA)
Sheath: Polyvinyl chloride (PVC)
YJY
YJLV
YJV22
YJV22
YJV32
YJLV32
Sectional area (mm2)
No. of core



Comments