fluoroplastic insulation and sheath 105degree Power Cable

  Performance of Usage
1) Rated voltage UO/U: 0.6/1kV
2) Max.working temperature allowed: 200ºC for cable with fluoroplastic insulation and sheath, 105ºC for cable with fluoroplastic insulation,105ºC heat resistanc and PVC sheath, and 180ºC for cable with fluo- roplastic insulation and silicon rubber sheath.
3) Max temperature of cable conductor is no more than 250ºC during short circuit (The longest lasting time is no more than 5s).
4) Temperature for installation is no less than -15ºC. 5: Bending radius of cable as follows:
It is no less than 20 times that of cable outer diam- eter for cable with single core
It is no less than 15 times that of cable outer diameter for cable with 3 cores
6: Power cable with fluoroplastic insulation and sheath has good features of chemical corrosion resis- tance, high temperature resistance and flame retardance.

2.2 Type and Description
TypeDescription
FFHigh temperature resistant power cable with F   
insulation and sheath
FF22High temperature resistant power cable with F   
insulation and sheath, steel tape armoring
(ZR)-FGHigh temperature resistant power cable with F   
insulation ( flame retardant)and silicon rubber sheath

(ZR)-FG22
High temperature resistant power cable with F   
insulation ( flame retardant), silicon rubber sheath and steel tape armoring

(ZR)-FV
High temperature resistant power cable with F
  insulation ( flame retardant), 105ºC heat resistance  and PVC sheath


(ZR)-FV22
High temperature resistant power cable with F 
insulation ( flame retardant), 105ºC heat resistance , PVC sheath and steel tape armoring




2.3 Specification


Type



Core number

Nominal
 cross section area

FF



1,2,3,4,5,

3+2,3+1

1.5~95

FF22


2.5~70

(ZR)-FG, (ZR)-FV


1.5~240

(ZR)-FG22,(ZR)-FV22


2.5~240


2.4 Technical Parameter
1) DC resistance of conductor at 20ºC shall meet the requirement of GB/T3956 standard.
2) Cable shall bear AC voltage test of 3500V for 5min without puncture of insulation.